Swaraj commented,
Hi All, I was able to resolve the issue with respect to subnet led and also with data interface part. So as mentioned anybus configuration was right, the drager LEL had same node address which we f...
-
Swaraj commented,
Hi Kyle, Yes I was able to read value from other registers like gas name, calibration date, but the address 507 which gives the actual gas reading, I was not able to see it in the anybus node monit...
-
Swaraj commented,
Hi Kyle, Thanks for the information, but I am unaware of the service init part. I will reach out to vendor for that. Regards Swaraj
-
Swaraj commented,
Its AB 7072-B. Regards Swaraj
-
Swaraj commented,
Hi Tim, Yes, it was showing red even with one. Tried powering off all the LEL still the red light was there. Kind Regards Swaraj
-
Swaraj commented,
polytron-8xx0-modbus-rtu-fieldbus-communication-9033781-ifu-en-us.pdf (2.6 MB) Hi this was used by the vendor to configure drager LEL. I Also found out, all LELs have same node address (1). To avid...
-
Swaraj commented,
Hi All, I started using Anybus gaetway for connecting to drager LEL head, which send data to gateway using Modbus RTU. I am trying to connect with the first node. I am successfully able to receive ...
-
Swaraj created a post,
Subnet LED Red
Hi All, Repeating my question, As I think the first one didn't get through. I have recently started using anybus gateway for building communication between drager LEL and L73s. I am have a healthy ...