PROCEDURE
During commissioning or maintenance, you indeed may want to isolate the truly bad tag from the others. Therefore, you have to disable the polling of tags in error. This can be done in the IO Server > Global Config parameters as shown below:
The relevant tag will no longer be polled, and it will no longer be included in a group (and hence it will not impact other tags).
At the creation of the Tags or at the initialization of an IOServer, all tags are considered as valid and are polled.
If repetitive errors occur on some Tags, these tags will be considered as invalid and will not be polled anymore!
A specific error message will be written in the event log.
This message is "Protocol Error while reading Tag (IOserver - TagName - Polling disabled for this tag)" (see example in figure below)
Invalid tags will be polled again when:
• the IOServer is started (i.e.: after a IOServer modification)
• a manual INIT of the IOServer is operated using the "Init" link next to the IOServer
selection box
• a modification of the Tag (in the I/O Server Setup part of Tag Setup)
Remind yourself to uncheck the "Disable Tags in Error" box, as soon as you have completed
your commissioning or maintenance task.