APPLICABLE PRODUCTS
IN770AIRxxx000
ISSUE
When scanning the Midea bus, the AC units can be found and read, but every command sent to the unit is reverted.
POSSIBLE CAUSES
There's an XYE Extension Kit and a central controller in the system. The central controller is connected to the CTR1 connector, and the Intesis gateway is connected to the CTR2 connector of the XYE Extension Kit.
SOLUTION
- Disconnect the gateway from the CTR2 connector and connect it to the ODU connector (see the image):
- Make sure that there are end-of-line (EOL) resistors on the XYE bus (120-ohm resistor on the first and last device).
ADDITIONAL INFO
The Intesis gateway features a built-in resistor that can be enabled using the DIP switch SW B, position 1.
Consult the IN770AIR Installation Sheet.