This document describes the different steps on checking the compatibility with Intesis AC Interfaces.
APPLICABLE PRODUCTS
- Mitsubishi Electric & Universal AC Interfaces: (IN770AIR00SO000, IN770AIR00MO000, IN485MIT001I000, INWMPMIT001I000, INKNXMIT001I000, INKNXMIT001I100, INMBSMIT001I000, INWFIUNI001I000, IN485UNI001I100, INWMPUNI001I000, INKNXUNI001I000).
PRE-REQUISITES
Considerations before reviewing a compatibility.
IN THIS ARTICLE
There are 2 main categories of gateways: One-to-One and Multi-Unit.
The One-to-One category is divided into 3 subcategories depending on the type of gateway: Universal IR, AC Connector and RC Connector. For this solution we have Universal IR and AC Connector available.
One-to-One
These gateways communicate with a single Indoor Unit and offer individual control points for the most relevant variables (on/off, setpoint, mode, fan speed, etc.).
Within this category there are 2 different types of Mitsubishi Electric gateways:
- Universal IR.
- AC Connector.
When checking a compatibility consider:
- Supported: Splits, Cassettes, Ducted and families Mr. Slim & City Multi.
- Not supported: Lossnay, Outdoor-Air Processing Units, Air to Water Booster Units, Air to Water HEX Units, Heat Pump and Outdoor Units.
-
If the Indoor Unit is compatible, the MELCloud Wi-Fi accessory we are compatible, but you cannot connect both at the same time.
-
Connectors CN51 + CN100 (with optional PAC-IT51AD-E adaptor).
-
Connectors CN52 + CN100 (with optional PAC-IT52AD-E adaptor).
-
Accessories: PAR-SA9FA-E, PAR-FA32MA, IR Kit receiver.
Universal IR
The Universal IR communicates via the Infrared receiver of the Indoor Unit
Multi-Unit
These gateways are connected to the Central Controller via Ethernet providing individual control points for the most relevant variables (on/off, setpoint, mode, fan speed, etc.) and signals from the Outdoor Units. These gateways use Intesis MAPS as Configuration Tool.
When checking a compatibility consider:
- Indoor Units cannot be connected directly to the gateways..
- Compatible with Central controllers: AG-150A, GB-50ADA or older, EB-50GU, AE-200, EW-50 or newer.
-
Not compatible with Central Controller without ethernet port.
ADDITIONAL INFO
To know more about how to user our AC Compatibility tool, check our Website
To know more about how to use our Intesis MAPS, check our Intesis MAPS eLearning