Deryck: Something odd is going on, I had to reset my password on hms this morning to login, and now my new password isn't working. Robert Akins
-
Deryck: Exactly what does a Modbus Illegal Data Address error mean to Netbiter? All my template register addresses are set to the values listed in the ModLon II installation guide for the default ...
-
Deryck: I did go in and remove the 40000 offset from all the parameters and now I can read several of them, looks like I may have to play with the multiplier a little bit in some cases. The genera...
-
Deryck: Here are examples of the template parameter settings I am using: And the same register in the ModLon II manual (Gen0):
-
Deryck: I really don't have any more information to refer to, other than the list of registers and the parameter they report, any multiplier or offset applicable, and the units of the value. For t...
-
Deryck: I will leave the issue for the "state' register for the moment, on to the other question. Registers 44 and 45 contain the engine runtime in seconds. Please see the following screen shot s...
-
What data type do you use for the low value? I can't seem to find anything that works. I tried 16-bit value and floating point, and neither one seemed to work.
-
OK, thank you sir, I will make that change and see what happens. Robert Akins Robert Akins Maintenance Repair Specialist II Denton County Facilities Department 750 S. Mayhill Rd. Suite B121 Denton...
-
Hi Deryck: I'm working on getting a different Netbiter set up, which is monitoring a slightly different controller, but which should read the state in the same manner, when I get data back from it ...
-
Deryck: Going back to the "State' parameter now. Below is a screen grab of the table shown in the Cummins manual for the genset controller, showing the values for the Modbus address 11. Each of t...