ericbucklen hizo un comentario,
Got it to work! Thanks for the assistance! The problem was that we didn't have the PLC IO matching the transactions in the X-gateway module
-
ericbucklen hizo un comentario,
We have configured the transactions (see photo). The PLC simply has the Anybus module as red (can't connect) and the only error/diagnostics we can get is a message that states "Not Reachable" The t...
-
ericbucklen creó una publicación,
AB9001 Profibus Configuration Error - PLC can't reach Anybus X-Gateway
Hello, I'm using an Anybus X-gateway modbus tcp client / profibus - AB9001-B (firmware 1.13). I've configured this module in my TIA Portal project using the HMSA1937.gsd file (v. 1.09) to talk to a...