Hi Gioele, are you aware that in PROFINET you have to drag those modules representing the desired process data map into consecutive slots of the device? And if you don't adhere to the default proc...
-
Hello Erik, I am sorry for the late reply. I will need to verify this on a Modbus Serial test setup, which I will have access to no sooner than upcoming Monday. In the meantime, would you be able t...
-
Hello Laura, on the one hand, you write that the MS LED is lit (I suppose green?) and the L/A LEDs on the Ethernet connector showing activity. This means that the ABCC40's state has reached WAIT_P...
-
Official comment I see that you've created a support ticket regarding your issue, where we will further pursue your matter.
-
Official comment Hello, judging from the information provided, my best guess is that your USB-RS232 adapter might not follow the RS232 specs. It should operate in the two domain (-15) -- (-3) V and (+15) -- (+3) V...
-
Official comment Good day sir, (1) I would definitely start out with the speed_example application as it exchanges two bytes in each direction. (2) Yes, process data corresponds to the EtherNet/IP terminology "impl...
-
Official comment Hi Gioele, defining default values this way only makes sense for ADIs with a APPL_WRITE_MAP_READ_ACCESS_DESC descriptor, i.e. for input process data from the PLCs point of view. Regarding the ESI f...
-
Official comment Hello Peter, speaking for HMS, I can say that we don't offer icon files for the Anybus X-gateway product series.
-
Hello, can you tell me the p/n of your Anybus Communicator?
-
Hello, actually, the B40 for EtherNet/IP doesn't support HTTPS, whereas the B40 for EtherNet/IP IIoT Secure (AB6990) does. For the latter, you'll need to install both a CA and a device certificate,...