It is working. Made a new cable using only pins 2, 3, and 5 to go between the scanner and the Anybus module. Both DEVICES supplying power to the same pin does not work.
-
HMS or Cognex, Needing some feedback on this please. Dennis c20d3d16bcd5059c63d1a9b403a33fc059201326.jpeg861Ã547
-
Deryck, Here is a schematic of the Datalogic Scanner that works fine with the Anybus Module. Notice that the external power (VCC) does not get connected at the Anybus module. c20d3d16bcd5059c63d1...
-
I sent pictures of the Hyper terminal screen yesterday (attached again). The first line is from the Datalogic scanner "10662073056871" The 2nd line is from the Cognex scanner. They are exactly the ...
-
Deryck, The Datalogic scanners sends data fine now (as I said below/last week). However, I am trying to upgrade to a Cognex 2D scanner. I have configured it with the same parameters: 9000,N,8,1 No...
-
I will give it a shot. Thank you.
-
Deryck, I installed the modified configuration file and then scanned a barcode. The data was successfully sent back to the PLC. THANK YOU. Question: Will the Anybus module send a null string (empty...