  • Dennis_Miller commented,

    It is working. Made a new cable using only pins 2, 3, and 5 to go between the scanner and the Anybus module. Both DEVICES supplying power to the same pin does not work.

  • Dennis_Miller commented,

    HMS or Cognex, Needing some feedback on this please. Dennis c20d3d16bcd5059c63d1a9b403a33fc059201326.jpeg861Ã547

  • Dennis_Miller commented,

    Deryck, Here is a schematic of the Datalogic Scanner that works fine with the Anybus Module. Notice that the external power (VCC) does not get connected at the Anybus module. c20d3d16bcd5059c63d1...

  • Dennis_Miller commented,

    I sent pictures of the Hyper terminal screen yesterday (attached again). The first line is from the Datalogic scanner "10662073056871" The 2nd line is from the Cognex scanner. They are exactly the ...

  • Dennis_Miller commented,

    Deryck, The Datalogic scanners sends data fine now (as I said below/last week). However, I am trying to upgrade to a Cognex 2D scanner. I have configured it with the same parameters: 9000,N,8,1 No...

  • Dennis_Miller commented,

    I will give it a shot. Thank you.

  • Dennis_Miller commented,

    Deryck, I installed the modified configuration file and then scanned a barcode. The data was successfully sent back to the PLC. THANK YOU. Question: Will the Anybus module send a null string (empty...

  • Dennis_Miller created a post,

    PLC no longer receiving data

    Deryck, I have connected to the Anybus 7007 module and uploaded the configuration file (Attached). I can scan a barcode and see the data if I start a logfile and then stop the log (see data_Log.jpg...