Swaraj
- Total activity 9
- Last activity
- Member since
- Following 0 users
- Followed by 0 users
- Votes 0
- Subscriptions 1
Comments
Recent activity by Swaraj-
Hi All, I was able to resolve the issue with respect to subnet led and also with data interface part. So as mentioned anybus configuration was right, the drager LEL had same node address which we f...
-
Hi Kyle, Yes I was able to read value from other registers like gas name, calibration date, but the address 507 which gives the actual gas reading, I was not able to see it in the anybus node monit...
-
Hi Kyle, Thanks for the information, but I am unaware of the service init part. I will reach out to vendor for that. Regards Swaraj
-
Its AB 7072-B. Regards Swaraj
-
Hi Tim, Yes, it was showing red even with one. Tried powering off all the LEL still the red light was there. Kind Regards Swaraj
-
polytron-8xx0-modbus-rtu-fieldbus-communication-9033781-ifu-en-us.pdf (2.6 MB) Hi this was used by the vendor to configure drager LEL. I Also found out, all LELs have same node address (1). To avid...
-
Hi All, I started using Anybus gaetway for connecting to drager LEL head, which send data to gateway using Modbus RTU. I am trying to connect with the first node. I am successfully able to receive ...