IP Transparency (IPT) passes the cellular IP address of a FlexEdge™ Cellular Modem sled through to one device connected to one of the FlexEdge's Ethernet ports. The device adopts the modem's IP settings and reaches the cellular network directly, as if it had the cellular connection itself.
Use it when a device behind the FlexEdge, such as a firewall, router, VPN concentrator or controller, should own the cellular IP address and handle the inbound traffic itself.
This article applies to Crimson 3.2. The FlexEdge in the example has a Cellular Modem sled (Modem 1), and the device is connected to Ethernet 2. For Sixnet SN and RAM series routers, see Sixnet SN/RAM Routers: How to Configure IP Transparency.
Note: In IP Transparency mode, the modem's Trust Status decides what reaches the device. With Untrusted, only traffic that matches a rule on the modem's Transparency tab is let through. With Trusted, traffic that matches no rule is forwarded to the device.
Note: Whether a device can be reached from the cellular network at all depends on the carrier, the APN and the network's reachability. For example, many carriers place SIMs behind carrier-grade NAT (CGNAT), which blocks inbound connections to the cellular IP address even when the forwarding rules are correct. Ask your carrier whether the SIM has a publicly reachable address.
Preparation
-
A FlexEdge with a Cellular Modem sled:
- A FlexEdge DA50A or DA70A equipped with a compatible Cellular Modem sled. Both models have two onboard Ethernet ports, so one port can be used for IP Transparency while the other stays available for local management. The DA10D and DA30D are not covered by this article.
- A SIM with an active data plan. Set its APN on the modem's SIM 1 tab (and SIM 2 on dual SIM modems).
-
The device that will receive the cellular IP address:
- Connected to the FlexEdge Ethernet port you will use for IP Transparency, in this article Ethernet 2.
- Its port set to obtain its IP address by DHCP. The FlexEdge runs a DHCP server on this port that gives the cellular IP settings to one device only. To give several devices access, connect a router or firewall here and put the other devices behind it.
-
Crimson 3.2 and a connection to the FlexEdge:
- Keep the other Ethernet port (here Ethernet 1) in its normal mode, so you can still reach the FlexEdge locally. Ethernet 1 is used for local management throughout this article.
Part 1: Prepare the Ethernet Port
Step 1: Add the Cellular Modem Sled
Skip this step if your database already shows Modem 1 under System Configuration > Network > Interfaces.
- Navigate to Device Configuration > Hardware Configuration > Sleds.
- Click the edit (pencil) icon for the sled slot, set Sled Type: Cellular Modem, and click OK.
- Click the red Hardware indicator in the status bar, click Commit Changes, and click Yes. Modem 1 now appears under Interfaces.
Step 2: Set the Ethernet Port to IP Transparency
- Navigate to System Configuration > Network > Interfaces > Ethernet 2, Settings Tab.
- Set the following:
- Port Mode: IP Transparency. The IP address settings of the port are grayed out, because the port takes its settings from the modem.
- Full Duplex and High Speed: leave at Automatic, so the port negotiates with the device.
Part 2: Bind the Modem to the Ethernet Port
Step 1: Set the Modem to IP Transparency
- Navigate to System Configuration > Network > Interfaces > Modem 1, Settings Tab.
- Set the following:
- Port Mode: IP Transparency.
- Target Interface: Ethernet 2. The target port must itself be in IP Transparency mode. Automatic selects the first Ethernet port that is in IP Transparency mode.
-
Trust Status:
- Untrusted (the default and recommended setting): only traffic that matches a forwarding rule (Part 3) is let in. Use Untrusted with explicit forwarding rules, each limited by a white list where you can.
- Trusted: traffic that matches no forwarding rule is forwarded to the device. Crimson warns that modems should be set to Untrusted unless you use a private APN, because Trusted disables most firewall protection.
Part 3: Decide What Reaches the Device and the FlexEdge
The modem's Transparency tab sets where inbound connections from the cellular network go: to the device (Client) or to the FlexEdge itself (Router). Its settings are available only in IP Transparency mode.
Note: The FlexEdge has two different web servers. The System Web Server is the device's diagnostic and status web pages. It uses HTTPS on TCP port 4443. The Crimson Runtime Web Server serves the web pages and content of your Crimson database. It listens on the port set in its own configuration, for example TCP port 80 for HTTP. The Runtime Web Server must be enabled in the database and be supported by the device's software group. To enable it, select the Web Server category in the Navigation Pane and set Enable Web Server on its root entry; the port it listens on is set on the same page. The two servers are separate, so a rule for one does not reach the other.
Step 1: Create a White List (Optional)
A white list limits a rule to traffic from known addresses, for example your control room.
- Navigate to System Configuration > Network > Firewall > Access Lists, White Lists Tab.
- Click the edit (pencil) icon on the empty row.
- Set the following:
- Label: a name for the list, for example Control Room.
- Address: the source address or network, for example 203.0.113.0.
- Mask: for example 255.255.255.0. Use 255.255.255.255 for a single address.
- Click OK. Repeat for each list you need.
Step 2: Add Forwarding Rules
- Navigate to System Configuration > Network > Interfaces > Modem 1, Transparency Tab.
- Under Forwarding Rules, click the edit (pencil) icon on the empty row.
- Set the following:
- Label: a name for the rule.
- Port: the inbound port on the cellular interface.
- Protocol: TCP, UDP or TCP+UDP.
- Target Device: Client to pass the traffic to the device, or Router to pass it to the FlexEdge itself.
- Target Port: the port the traffic is forwarded to. Unchanged (the default) keeps the inbound port. The table shows Unchanged as 0.
- White List: Allow All, or a white list from Step 1 to accept traffic from that list only.
- Click OK. Repeat for each port you need.
Example 1: pass Modbus TCP connections on port 502 through to the device.
Example 2: reach the Crimson Runtime Web Server over the cellular connection. Keep inbound port 8080 for the FlexEdge: set Target Device to Router, Target Port to 80, and White List to the Control Room white list. Router sends matching inbound traffic to the FlexEdge itself instead of the device.
Example 3: reach the System Web Server. Add a rule with Port 4443, Protocol TCP, Target Device Router, Target Port 4443, and a white list in White List. Do not leave this rule open to Allow All.
Note: Examples 2 and 3 are based on the Crimson 3.2 Software Guide. They have not been tested on a FlexEdge in IP Transparency mode.
Step 3: Set How Pings Are Handled
- Under ICMP Forwarding, set the following:
-
Target Device:
- Client (the default): the device answers inbound pings.
- Router: the FlexEdge answers them.
- Blocked: inbound pings are not processed.
- White List: Allow All, or a white list to accept pings from that list only.
-
Target Device:
Part 4: Download and Check
Step 1: Send the Database
- Save the database and send it to the FlexEdge over Ethernet 1 or another connection that doesn't depend on Ethernet 2.
- Connect the device to Ethernet 2, if it isn't already, and let it obtain its address by DHCP.
Step 2: Check the Device's Address
- On the connected device, check that it has received an IP address by DHCP.
- Open the FlexEdge System Web Server (HTTPS, TCP port 4443) through the Ethernet port that is not set to IP Transparency, here Ethernet 1.
- Check the following:
- Interface Status on the Home page.
- The cellular modem's Sled Status page.
- Diagnostic > Network Info > Network Config.
- Compare the cellular IP address with the address assigned to the connected device. In IP Transparency mode they should match. Diagnostic > Network Info > DHCP Leases may also show lease information.
Part 5: Frequently Asked Questions (FAQ)
Question: Can more than one device use the cellular IP address?
Answer: No. The DHCP server on the IP Transparency port gives the address to a single device. If several devices need access, connect a router or firewall to that port and put the devices behind it.
Question: What does the device receive besides the IP address?
Answer: The connected Ethernet device must be configured as a DHCP client. When IP Transparency is active, the FlexEdge uses DHCP to assign the cellular IP address and associated network settings to a single connected device. You can inspect the subnet mask, default gateway, DNS servers and lease duration on the connected device.
Question: Which inbound traffic reaches the device?
Answer: With the modem's Trust Status set to Untrusted, only traffic that matches a forwarding rule with Target Device Client. With Trusted, also all traffic that matches no rule. Traffic matching a rule with Target Device Router goes to the FlexEdge, not the device.
Question: How do I reach the FlexEdge over the cellular connection?
Answer: Add a forwarding rule with Target Device Router for the port you want to use, as in Part 3, Examples 2 and 3, and limit it with a white list. Whether the connection arrives also depends on the carrier, APN and CGNAT, as described at the start of this article.
Question: Can I use Ethernet 1 instead of Ethernet 2?
Answer: Yes. Set the port you want to IP Transparency and select it as the modem's Target Interface. Make sure you can still reach the FlexEdge through another port.
References
-
Crimson 3.2 Software Guide (September 2025, LP1153 Revision F):
- Ethernet port settings and the IP Transparency port mode: pages 40-41.
- Modem Settings tab (Port Mode, Target Interface, Trust Status): page 46.
- Modem SIM 1 and SIM 2 tabs (APN): page 48.
- Modem Transparency tab (ICMP Forwarding and Forwarding Rules): page 49.
- System Web Server (HTTPS on port 4443) and its home, diagnostic and sled status pages: pages 93 and 96-103.
- Crimson Runtime Web Server settings: pages 245-249.
Disclaimer
It is the customer's responsibility to review the advice provided herein and its applicability to the system. Red Lion makes no representation about specific knowledge of the customer's system or the specific performance of the system. Red Lion is not responsible for any damage to equipment or connected systems. The use of this document is at your own risk. Red Lion standard product warranty applies.
HMS Technical Support
If you have any questions or trouble contact HMS Technical Support by clicking here.