Introduction
When you connect to a FlexEdge™ device through Talk2M with eCatcher, you are not connected to one device. The VPN gives you routed (Layer 3) access to the whole network you select for Talk2M on the FlexEdge. By default, every device on that network can be reached by every Talk2M user who can connect to the FlexEdge.
Read this article before you finish the Talk2M enrollment of your FlexEdge, so you can choose that network on purpose.
Example Setup
All IP addresses in this article are examples only.
- FlexEdge LAN: 172.31.252.0/24.
- FlexEdge: 172.31.252.1.
- PLC: 172.31.252.11.
- HMI: 172.31.252.12.
What a Talk2M User Can Reach
In eCatcher, the device's Properties include LAN & Firewall > Modify LAN Subnet. The subnet you choose there is the FlexEdge network that the Talk2M VPN connects to.
With the example LAN selected, a connected Talk2M user can reach:
- The FlexEdge itself (172.31.252.1).
- The PLC (172.31.252.11) and the HMI (172.31.252.12).
- Any other device with an address on that subnet (172.31.252.1 to 172.31.252.254).
Note: If the network you select is also your plant or office network, every computer, server and controller on it is open to your Talk2M users, not only the machine you meant to reach.
Best Practice: Keep Separate WAN and LAN Networks
HMS recommends using the FlexEdge as the boundary between the outside connection and your control network:
-
WAN:
- Connect one FlexEdge interface to the network that gives it Internet access. Talk2M uses this connection to reach the Talk2M servers.
-
LAN:
- Connect the devices your remote users need, such as the PLC and HMI, to a separate FlexEdge interface on its own subnet.
- Select only this LAN subnet in eCatcher's Modify LAN Subnet.
-
Field devices:
- Don't place field devices directly on a network that can be reached from outside.
To set up the FlexEdge's WAN and LAN interfaces, see FlexEdge DA50A/DA70A Ethernet, Wi-Fi and Cellular WAN Setup.
Limiting Access Within the Selected Network
Nothing limits access within the selected network by default. At the Standard firewall level, eCatcher itself says that Talk2M users may connect to all devices on the LAN, whether they are listed or not:
If remote users should reach only some devices, use eCatcher's firewall for the FlexEdge.
- In eCatcher, open the FlexEdge's Properties.
- Under LAN & Firewall, click Configure LAN Devices & Firewall....
- Click Add LAN Device... and add each device your remote users need, such as the PLC and the HMI.
-
Under Firewall, move the slider to High. Only the devices you listed are then reachable by connected users.
- Click OK.
For more about these settings, see the eCatcher help on device firewall rules.
Note: Don't rely on the FlexEdge's own firewall to limit Talk2M users. The firewall pages in the FlexEdge's System Configuration (Access Lists, Untrusted Traffic and Routing Filters) don't offer the Talk2M connection as an interface, and their rules don't apply to Talk2M traffic.
A separate LAN that holds only the devices your remote users need is the most dependable limit.
Frequently Asked Questions (FAQ)
Question: Is Talk2M access limited to one device by default?
Answer: No. A connected user can reach every device on the subnet selected in Modify LAN Subnet, including the FlexEdge itself.
Question: Can I use the FlexEdge firewall to limit what Talk2M users reach?
Answer: No. Use eCatcher's firewall, as described above, or a separate LAN.
Question: Which Crimson version do I need for Talk2M on a FlexEdge?
Answer: Crimson 3.2.1053 or later.
Question: Where do I set up Talk2M on the FlexEdge?
Answer: On the Talk2m Integration page of the FlexEdge web interface. For the full procedure, see Secure Remote Access to FlexEdge Using Talk2m.
Disclaimer
It is the customer's responsibility to review the advice provided herein and its applicability to the system. Red Lion makes no representation about specific knowledge of the customer's system or the specific performance of the system. Red Lion is not responsible for any damage to equipment or connected systems. The use of this document is at your own risk. Red Lion standard product warranty applies.
HMS Technical Support