This article explains what to do when you are unable to configure your PROFIBUS DP Device Anybus Communicator due to the address having the static value 4095.
APPLICABLE PRODUCTS
ABC3000
ABC3100
ABC3200
ABC3300
ABC4014
ABC4018
ABC4023
ABC4028
PRE-REQUISITES
A PROFIBUS DP Device Anybus Communicator.
Access to the web interface of the Anybus Communicator.
PROBLEM DESCRIPTION
You open the internal configuration web interface of your Anybus Communicator, and you notice that the Profibus address is 4095 and you are unable to change it.
You get an error similar to this:
SOLUTION
Check the rotary switches at the top of the Anybus Communicator.
This issue occurs when all three rotary switches are in the "F" position. 0xFFF = 4095 in decimal. This is not a valid PROFIBUS address.
If you want to set the PROFIBUS address with the rotary switches, keep the rear switch to "0", then use the last two switches to set the address and restart the Anybus Communicator.
If you would like to be able to set the address on the web interface, then set all three rotary switches to the "0" position and restart the Anybus Communicator.
The issue should now be solved.