Abstract
We had a request from a customer wanting to know if we could use 12650 tags in our OPCUA server, so this is the report on the testing
Hardware:
DA50, DA70
Software:
Crimson 3.2.1060 and Higher
Section 1:
Using a DA70 group 4 with Crimson 3.2.1060 as the firmware base, a database was created with 12650 tags and placed into the OPCUA server setup
This was tested with Kepware KepServer Version 7.141 OPCUA client
After doing the setup on both devices it was determined that the Kepware OPCUA client was able to successfully download the DA70 OPCUA model and pull it into it's Quick Client and talk to all of the tags in less than 2 mins from start to full communications.
It was also discovered during this that if you used Arrays, any amount of arrays above 1000 would make the DA70 do a constant reboot and after 3 times it would clear the configuration.
End Results:
Using 12650 tags in our OPCUA Server can be successfully done using Kepware's OPCUA client
No testing of using the DA70 OPCUA client has been done
Further testing with up to 25000 tags will be tested for the OPCUA server and see how that does