It has been determined that the original calibration that was performed by manufacturing had a problem with the input signal scaling operation. It was scaled improperly, so when the end user tries to scale the meter in 4 - 20ma or 0 - 10Vdc It has a problem. It will display OLOL.
TO RECALIBRATE THE PROCESSOR CHIP:
Press PAR to see Pro No
press F1 nine times to see 9-FCS
press PAR to see D-LEU = 3
press PAR to see CODE = 50
press F2 button to see CODE = 48
press PAR to see (RANGE to be calibrated)
Press the arrow keys to select the correct RANGE to calibrate.
press PAR to see 0.02A range
be sure the input is connected to the common (shorted) and press PAR
you will see - - - - -
when zero calibration is completed, it will display 20 mA
apply the 20mA signal to the input and Common and press PAR.
you will see - - - - -
when 20 mA input is completed, it will say Pro No.
press PAR to see END.
Now the processor should be calibrated correctly.