This article explains the procedure to scale a PAXS0000 Strain Gage panel meter. The primary information is taken from the load cell name plate. We need the mV/V rating of the load cell.
APPLICABLE PRODUCTS
The PAXS0000 (AC powered).
The PAXS0010 (DC powered).
PRE-REQUISITES
You first need the mV/V rating from the load cell; this is based upon 1 Vdc excitation.
You multiply that by 10 because we use 10 Vdc Excitation. (e.g. 3.3 mV/V x 10V = 33.0 mV)
In the RANGE selection, you can use 0.02u or 0.2u. Here you would select the 0.2u setting.
The 0.02u only goes to 24 mV MAX.
IN THIS ARTICLE
ITEM 1
To start programming the PAXS0000 meter, press the PAR button to see Pro No.
- press F1 button once to see 1-INP
- press PAR to see RANGE = 0.02u (here you select the correct RANGE based upon the load cell information)
- press PAR to see DECPT. Use F1/F2 to select the number of decimals you want in your display.
- press PAR to see ROUND = leave at default
- press PAR to see FILTR = leave at default.
- press PAR to see BAND = leave at default.
- press PAR to see PTS = This is normally set to two. They represent MIN weight on the scale and MAX weight on the scale.
- press PAR to see STYLE = KEY. You can press F1 and use APLY if you are setting the scale with actual weights.
- press PAR to see INP-1 = This will be the nominal reading with no weight on the scale.
- press PAR to see DSP-1 = This should be ZERO.
- press PAR to see INP-2 = After loading the scaling weights, this will be the reading with a determined amount of weight on the scale.
- press PAR to see DSP-2 = This should be the actual weigh that was applied at INP-2.
- press PAR to see Pro No.
- press PAR to see END.
- This will complete the Input programming.
ITEM 2
- Additional programming can be completed in MOD #2-FNC.
- If you want to TARE (ZERO) the display, you can use the RST button and program it to RST = rEL
- press PAR button to see Pro No
- press F1 button two times to see 2 - FNC
- press PAR once to see USR-1 = NO (this can be programmed for a Remote Reset option)
- press PAR once to see USR-2 = NO
- press PAR once to see USR-3 = NO
- press PAR once to see F1 = NO
- press PAR once to see F2 = NO
- press PAR once to see RST = NO
- press F1 button two times, till you see REL
- press PAR once to see SC-F1 = NO
- press PAR once to see SC-F2 = NO
- press PAR once to see Pro No
- press PAR once to see END.
- Now pressing the RST button should ZERO the display.
- Look for additional programming assistance for setting up Setpoint values.
Additional Info
Link PAX Analog Product Manual
HMS Support
If you need additional assistance, please submit a request through the support portal: