APPLICABLE PRODUCTS
Model CTR – True RMS AC Current Transducer
PAXD0000 – DC Voltage and DC Current meter
PAXP0000 – DC Process Meter
PAXLA000 – Lite series DC Meter
PRE-REQUISITES
The CTR Current Transducer has 2 different models.
Each model has a 3-step program jumper for 3 input values.
Wiring of the CTR is basic.
IN THIS ARTICLE
Programming the PAXD and PAXP.
Press the PAR button to see Pro No
Press the F1 once to see 1-INP
Press the PAR button RANGE = 0.02A
Press the PAR button to see DECPT = 0
Press the PAR button to see ROUND = 1
Press the PAR button to see FILTR = 1.0
Press the PAR button to see BAND = 10
Press the PAR button to see PTS = 2
Press the PAR button to see STYLE = KEY
Press the PAR button to see INP-1 = 4.00
Press the PAR button to seeDSP-1 = 0
Press the PAR button to see INP-2 = 20.00
Press the PAR button to see DSP-2 = 100 (this will be the MAX value)
Press the PAR button to see Pro No
Press the PAR button to see END.
Programming the PAXLA000
Press PAR to see Pro No
Press SEL to see 1-INP
Press PAR to see RANGE = 0.02A
Press PAR to see DECPT = 0
Press PAR to see OFSET = 0
Press PAR to see FILTR = 1
Press PAR to see BAND = 10
Press PAR to see STYLE = KEY
Press PAR to see INP-1 = 4.00
Press PAR to see DSP-1 = 0
Press PAR to see INP-2 = 20.00
Press PAR to seeDSP-2 = 100 (this will be the MAX value)
Press PAR to see USR IN = NO
Press PAR to see Pro No
Press PAR to see END.
ADDITIONAL INFO
Additional Output cards can be added
The PAXD and the PAXP can have added Setpoint cards added for outputs.
The PAXD and the PAXP will support a Retransmit Analog card for an Analog output.
The PAXD and the PAXP can also use a Communications output card.
Wiring and ordering information can be found in the manual.
The PAXLA00 “does not support” Analog or Comms cards for outputs.