Tank Fill App: CUB5P, CUB5I, CUB5V
Description text that describes what the information in this article is related to. Make sure that the text includes the product name and the summary of the issue the article solves in the first 120 characters (Mandatory)
APPLICABLE PRODUCT MODELS
CUB5PR00 - CUB5PB00
CUB5IR00 - CUB5IB00
CUB5VR00 - CUB5VB00
PRE-REQUISITES
The CUB5P has an internal jumper that needs to be set to the correct input signal value.
The CUB5I has 4 different internal inputs that need to be set per the input signal.
The CUB5V has an internal jumper that needs to be set to the correct input signal value.
IN THIS ARTICLE (Mandatory)
ITEM 1
Table of content
- Determine the type of input signal being used and set the internal jumper accordingly.
- Program the Input parameters in Module #1-INP
- Programming any Setpoint output devices required in Module 4-SPT
- Program the Serial output in Module #5-SER if required.
- Instructions for Step 1:
Set the internal jumpers per the instructions for each display.
CUB5P CUB5I CUB5V
Instructions for Step 2:
Press and hold the SEL button until you see Pro No
Press RST button once to see 1-INP
Continue pressing SEL button to see RANGE = (select the correct input range)
Continue pressing SEL to see DECPT = (select number of decimals in your display)
Continue pressing SEL to see OFSET = usually left at ZERO
Continue pressing SEL to see FILTR = 1
Continue pressing SEL to see BAND = 120
Continue pressing SEL to see STYLE = KEY
Continue pressing SEL to see INP-1 = 4.00 (if using a current input signal)
Continue pressing SEL to see DSP-1 = 0
Continue pressing SEL to see INP-2 = 20.00 (if using a current input signal)
Continue pressing SEL to see DSP-2 = 100 (or what your MAX signal will display)
Continue pressing SEL to see USR IN = NO
Continue pressing SEL to see Pro No
Continue pressing SEL to see END.
Instructions for Step 3:
Press and hold the SEL button until you see Pro No
Press RST button 4 times to see 4-SPT
Continue pressing SEL to see SPSEL = NO (press RST to change to SP-1)
Continue pressing SEL to see ENB-2 = NO
Continue pressing SEL to see ACT-1 = HI-UB
Continue pressing SEL to see SPT-1 = (your setpoint value)
Continue pressing SEL to see HYS-1 = 2
Continue pressing SEL to see TON-1 = 0.0
Continue pressing SEL to see TOF-1 = 0.0 Continue pressing SEL to see RST-1 = AUTO
Continue pressing SEL to see REN-1 = YES
Continue pressing SEL to see STB-1 = NO
Continue pressing SEL to see CHC-1 = NO
Continue pressing SEL to see Pro No
Continue pressing SEL to see END
Instructions for Step 4:
Press and hold the SEL button until you see Pro No
Press RST button 5 times to see 5-SER
Continue pressing SEL to see BAUD = 9600
Continue pressing SEL to see DATA = 7-bit
Continue pressing SEL to see PAR = Odd
Continue pressing SEL to see ADDr = 00
Continue pressing SEL to see ABBr = NO
Continue pressing SEL to see OPT = NO
Continue pressing SEL to see Pro No
Continue pressing SEL to see END.