Compatible Devices
Verified Device
Accessible Data
Mnemonic → W
Parameter → Parameter Address
Function → Read / Write [yaskawa-sgdh-g3 | Word]
- Programmer enters parameter number in hexadecimal
- Driver performs direct read/write to that address [yaskawa-sgdh-g3 | Word]
Parameter Address Areas
| Address Range |
Description |
| 0000–0FFF |
Parameter area |
| 1000–1FFF |
Temporary parameter area |
| 2000–2FFF |
Operation area |
| 3000–3FFF |
Trace area |
| 5000–5FFF |
Trace control area |
| 8000–8FFF |
Monitor area |
[yaskawa-sgdh-g3 | Word]
Notes
- No validation of parameter selection
- Programmer must ensure valid address usage [yaskawa-sgdh-g3 | Word]
-
String data not supported
Cable Information
RS232
| Signal |
G3 |
SGDH |
| Tx |
Pin 5 |
Pin 4 |
| Rx |
Pin 2 |
Pin 2 |
| Common |
Pin 3/4 |
Pin 14 |
RS422
| Signal |
G3 |
SGDH |
| TxA |
Pin 2 |
Pin 4 |
| TxB |
Pin 1 |
Pin 3 |
| RxA |
Pin 3 |
Pin 2 |
| RxB |
Pin 4 |
Pin 1 |
| Common |
Pin 6 |
Pin 14 |
Note: RS422 wiring based on equivalent CN6 mapping [yaskawa-sgdh-g3 | Word]
RS485
| Signal |
G3 |
SGDH |
| TxA / RxA |
Pins 2 / 3 |
Pins 2 / 4 |
| TxB / RxB |
Pins 1 / 4 |
Pins 1 / 3 |
| Common |
Pin 6 |
Pin 14 |
RS485 Note
© HMS Networks AB 2025