Compatible Devices
- T‑Series PLC
- EX‑Series PLC
- S‑Series PLC [toshiba | Word]
Verified Devices
- T2 PU224 PLC
- M2O PROSEC EX‑Series PLC
- S2E PU612E PLC [toshiba | Word]
Accessible Data
D → Data Registers → 0–9999 [toshiba | Word]
F → File Registers → 0–32767 (S‑Series only) [toshiba | Word]
XW → Input Words → 0–999 [toshiba | Word]
YW → Output Words → 0–999 [toshiba | Word]
RW → RW Registers → 0–9999 [toshiba | Word]
T → Timers → 0–999 [toshiba | Word]
C → Counters → 0–999 [toshiba | Word]
Notes
- For T and EX series:
- Hundreds digit ignored [toshiba | Word]
- For T / S series:
- Must select:
- Device‑ON
- Device‑OFF
- Status
- Status → read only
- Device‑ON/OFF controls timer/counter behavior [toshiba | Word]
- Must select:
Data Format
Long Values
- Stored across 2 registers
- Lower register = high word
Example:
Reg100 = 1111
Reg101 = 2222
Returned = 11112222 [toshiba | Word]
Real Values
- Lower register = low 16 bits
Example:
Hex C1480000 = -12.5
Reg100 = 0000
Reg101 = C148 [toshiba | Word]
Cable Information
RS485
G3 Pin 1 (TxB) → PLC RxA
G3 Pin 2 (TxA) → PLC RxB
G3 Pin 3 (RxA) → PLC TxB
G3 Pin 4 (RxB) → PLC TxA
G3 Pin 6 (Comm) → PLC Comm [toshiba | Word]