Application Note
Refer to the Modbus TCP/IP Master Application Note for assistance in configuring the properties of the port, the driver, and the device. [g3-scheide...uetsx57tcp | Word]
Accessible Data
| Selections | Data Type | Equivalent Modbus Register |
|---|---|---|
| MW0 – MW65534 | 16 bits | 400001 – 465535 |
| IW0 – IW65534 | 16 bits | 300001 – 365535 |
| M0 – M65534 | 1 bit – Internal | 000001 – 065535 |
| I0 – I65534 | 1 bit – Input | 100001 – 165535 |
| MDW0 – MDW65534 | 32 bits | 400001,400002 – 465534,466535 |
| MF0 – MF65534 | 32 bit Real | 400001,400002 – 465534,466535 |