Compatible Devices
FloBoss 103/104 Series
ROC800 [g3-roc2 | Word]
Verified Device
FloBoss 103
ROC800 [g3-roc2 | Word]
Overview
The Emerson FloBoss/ROC serial communications driver supports FloBoss/ROC devices that follow the same implementation as the FloBoss 100 series or ROC800.
For full support of other ROC protocol devices, contact technical support. [g3-roc2 | Word]
Device Configuration
A security section is available within the device configuration in Crimson.
Configure:
- Operator ID
- Password
- Access Level (if required)
These settings are used during communication with the Emerson device. [g3-roc2 | Word]
Accessing Data
A TLP selection dialog in Crimson provides:
- Short name
- Numeric TLP designation
- Data type [g3-roc2 | Word]
TLP Data Format
Numeric TLP values are interpreted as:
XXTTLLPP
Where:
- TT = Point Type
- LL = Logical Number
- PP = Parameter Number [g3-roc2 | Word]
String Data Handling
- Assign string data to a string tag
- Set packing to ASCII BigEndian
- Maximum length: 60 characters
Important:
- If writing a string with the same first 4+ characters as the existing value, clear the string first before writing the new value [g3-roc2 | Word]
Time Display
Use Crimson’s Time and Date primitive for displaying device time:
- Point Type 12, Parameter 8
- Point Type 136, Parameter 7 [g3-roc2 | Word]
Cable Information
FloBoss 103 LOI Port
| G3 RS232 Port | FloBoss 103 LOI Port |
|---|---|
| 2 - Rx | Tx |
| 5 - Tx | Rx |
| 3,4 - Common | 5 - Common |
ROC800 CPU RS232C COM2 Port
| G3 RS232 Port | ROC800 COM2 Port |
|---|---|
| 2 - Rx | 2 - Tx |
| 5 - Tx | 1 - Rx |
| 3,4 - Common | 5 - Common |
© HMS Networks AB 2025