Compatible Devices
Mitsubishi A, Q or FX series PLC fitted with appropriate Ethernet communications module. [g3-micromo...ndedmodbus | Word]
Verified Device
Mitsubishi Q02H CPU via QJ71E71-100 Module
Mitsubishi Fx3u-32M CPU via FX3u-ENET Module [g3-micromo...ndedmodbus | Word]
Supported Communication Modes
Only Binary Code communications are supported. [g3-micromo...ndedmodbus | Word]
Accessible Data
| Prefix | Description | Access |
|---|---|---|
| X | Input | Read / Write |
| Y | Output | Read / Write |
| M | Internal Relay | Read / Write |
| F | Annunciator | Read / Write |
| B | Link Relay | Read / Write |
| D | Data Register | Read / Write |
| W | Link Register | Read / Write |
| T | Timer Current Value | Read / Write |
| C | Counter Current Value | Read / Write |
Cable Information
Standard 10-Base-T Ethernet Cable [g3-micromo...ndedmodbus | Word]
Mitsubishi FX Quick Configuration Guide via FX Configurator-EN
In GX Developer, select Tools > FX special function utility.
Place Photo Here
In FX Configurator-EN, select the Module number corresponding to the position of the ENET module.
Place Photo Here
Click on the “Operation settings” button.
Place Photo Here
Set the IP Address according to the network application. Configure all other settings as required.
Click on the “Open settings” button.
Place Photo Here
Configure a TCP setting:
- Host Station Port Number should match the configured TCP port
Select the “Write” button within FX Configurator-EN to send the configuration to the FX Ethernet module.
Note: The FX Ethernet module must be re-initialized before the new settings take effect. [g3-micromo...ndedmodbus | Word]