This protocol supports EtherNet/IP explicit messages with embedded PCCC (DF1 style) commands..docx&action=default&mobileredirect=true) [g3-abpccc (1) | Word]
Compatible Devices
Allen-Bradley PLC-5 with PCCC support
Allen-Bradley SLC with PCCC support
Allen-Bradley ENI Module
Allen-Bradley ControlLogix (INT, DINT, REAL data types only).docx&action=default&mobileredirect=true) [g3-abpccc (1) | Word]
Verified Device
MicroLogix 1500 via ENI Module.docx&action=default&mobileredirect=true) [g3-abpccc (1) | Word]
Device Selection
Many PLC-5 users may use the SLC device selection. In order to use the SLC device selection, the PLC-5 processor must have the ability to respond to “protected typed logical write with three address fields” commands..docx&action=default&mobileredirect=true) [g3-abpccc (1) | Word]
Accessible Data
| **Prefix** | **Description** |
|---|---|
| O | Outputs |
| I | Inputs |
| S | Status |
| B | Bits |
| N | Integers |
| T | Timers |
| C | Counters |
| F | Float Point |
| L | Long Word |
| R | String Area (80 characters support) * |
* When mapping the String Area to String Arrays, 80 characters per string should be used..docx&action=default&mobileredirect=true) [g3-abpccc (1) | Word]
Cable Information
Standard 10-Base-T Ethernet Cable.docx&action=default&mobileredirect=true) [g3-abpccc (1) | Word]