Compatible Devices
Keyence KV Series
Verified Device
Keyence KV-16AR
Accessible Data
| **Prefix** | **Description** | **Range** |
|---|---|---|
| DM | Data Memory | 0 - 9999 |
| TM | Temporary Memory | 0 - 99 |
| CC | Counter Current Values | 0 - 999 |
| CP | Counter Preset Values | 0 - 999 |
| TC | Timer Current Values | 0 - 999 |
| TP | Timer Preset Values | 0 - 999 |
Communication Cable
Place Photo Here
Communication Cable, G3 / Modular Controller / Data Station Plus to Keyence KV Series.
# CBLKEY01 – 10’ long
RS232 PORT
(TO KEYENCE KV SERIES)
5
1
2
4
3
6
| Connections | |||
|---|---|---|---|
| FROM RLC UNIT | Name | CONNECTER PINOUT | |
| RED LION RJ12 | KEYENCE KV RJ11 (NUMBERING FLIPPED) | ||
| 1 | CTS | 1 | - |
| 2 | Rx | 2 | 5 |
| 3 | COMM | 3 | 4 |
| 4 | COMM | 4 | - |
| 5 | Tx | 5 | 3 |
| 6 | RTS | 6 | - |
Place Photo Here
Place Photo Here
The above table denotes the pin names of the RS232 port. When connecting, the pin name at the RS232 port is connected to the opposite of that pin name at the destination device.
RS232 PORT (FROM RLC UNIT)
© HMS Networks AB 2025