Downloads
1. Communication Cable – G3 / Modular Controller / Data Station Plus to Siemens S7 via PPI / Simovert via USS
cblsie01_0.docx
Cable Details
- Cable Part Number: CBLSIE01
- Length: 10 feet
- Application:
- G3 / Modular Controller / Data Station Plus to Siemens S7 via PPI
- G3 / Modular Controller / Data Station Plus to Siemens Simovert via USS
- Interface: RS‑485
Connector Information
- Controller Side: RJ45
- PLC / Drive Side: DB9 Male
Connector Pinout
| FROM RLC UNIT | Signal Name | RJ45 Pin(s) | DB9 Male Pin |
|---|---|---|---|
| 1 | TxB | 1 | 3 |
| 2 | TxA | 2 | 8 |
| 3 | RxA | 3, 8 | — |
| 4 | RxB | 4, 7 | — |
| 5 | TxEN | 5 | — |
| 6 | COMM | 6 | 5 |
| 7 | TxB | 4, 7 | — |
| 8 | TxA | 3, 8 | — |
Wiring Notes
- The table above denotes the pin names of the RS‑485 port.
- When connecting devices, the pin name at the RS‑485 port is connected to the opposite pin name at the destination device.
- Pins not explicitly shown as connected are not used.
© HMS Networks AB 2025