1. Communication Cable – G3 / Modular Controller / Data Station Plus to Mitsubishi FX0 & FX0N
cblmit02_0.docx
Cable Details
- Cable Part Number: CBLMIT02
- Length: 10 feet
- Application: G3 / Modular Controller / Data Station Plus to Mitsubishi FX0 & FX0N (RS‑485)
Connector Information
- Controller Side: RJ45
- PLC Side: Mini‑DIN 8
Connector Pinout
| FROM RLC UNIT | Signal Name | RJ45 Pin | Mini‑DIN 8 Pin |
|---|---|---|---|
| 1 | TxB | 1 | 2 |
| 2 | TxA | 2 | 1 |
| 3 | RxA | 3 | 4 |
| 4 | RxB | 4 | 7 |
| 5 | TxEN | 5 | — |
| 6 | COMM | 6 | 3 |
| 7 | TxB | 7 | — |
| 8 | TxA | 8 | — |
| — | SHIELD | — | — |
Wiring Notes
- The table above denotes the pin names of the RS‑485 port.
- When connecting devices, the pin name at the RS‑485 port connects to the opposite pin name at the destination device.