This Article to assist users how to scale Panel Meters with measuring length by using an encoder. Units of measure will be in feet.
APPLICABLE PRODUCTS
PAXI0020 - Count/Rate meter powered by 85-250 Vac.
PAXI0030 - Count/Rate meter powered by 11 to 36 Vdc, 24 Vac.
PAXC0020 - PAX® Dual Counter, AC-Powered
PAXC0030 - PAX® Dual Counter, DC-Powered
ZCH0500C - Encoder for testing.
PRE-REQUISITES
The PDF manual is attached below.
Setting the Dip switches for Encoder input.
Dip switches are #1 = Logic; #2 = Sink; #3 = High Frequency. 4, 5 and 6 are for Input B.
IN THIS ARTICLE
Item 1: We will start with the wiring with the PAXI0020 and go over wiring of the encoder (ZCH0500C). Then we will dive into the scaling process and explain how to calculate the scale factor.
Attached is the wiring diagram for using an encoder that has Quadrature Output. see the diagram below.
The ZCH encoder will have 4 wires Red = 8 - 28Vdc; Black = Common; White = Input A; Green = Input B. The encoder will output 500 Pulses Per Revolution. The dip switches above are configured for Sinking.
The scaling is calculated as follows:
The Scaling is performed in (1-INPUT) and you will need to press the (PAR) button till you see Pro No, then Press the (F1) button once until you see I - INPUT.
press PAR to see Pro No
press F1 once to see 1-INP
press PAR to see A CNT = CNT (press F1 to set this to QUAD1)
press PAR to see ARESET = ZERO
press PAR to see ADECPT = 0
press PAR to see ASCFAC = 1.00000
press PAR to see ASCALR = 1
press PAR to see ACNTLD = 500 (not used in this example)
press PAR to see A P-UP = NP
press PAR to see PrSEN = NO
press PAR to see B CNT = NONE
press PAR to see Pro No
press PAR to see END
Pressing the RST button should reset the counter to zero.
See below some useful information calculating the Scale Factor:
ADDITIONAL INFO
Contact Tech Support if you have additional questions.
I have included Links to the Product manuals
HMS Support
If you have any questions or need additional assistance, please submit a request to our Technical Support team using the following link: