This meter is powered from 10 to 30 Vdc power only. Power supply is needed with 120/240 Vac power.
This article will help in explaining the programming procedure of the PM500A Analog input meter.
This meter is used for +/- 0 to 2 A DC input, +/- 0 to 60 V DC input.
Also allows inputs from Thermocouples, RTD sensors and Resistance up to 10 K ohms.
It has two NPN/PNP transistor outputs preinstalled.
It can have additional Relay outputs with a relay plug-in module installed. 2-relay or 4-relay.
It can have Communications and Ethernet modules added.
You can add an Analog Output module for an Analog output signal.
APPLICABLE PRODUCTS
This setup guide covers the following meters:
PM500A0400800F00 4.3" Analog Input Graphical Panel Meter
PM500A0301600F00 3.5" Analog Input Graphical Panel Meter
ADDITIONAL INFO
Programming Methods
There are several methods to program a PM-50. On first power up, there is a default configuration that allows you to configure using the Initial Setup Wizard (also referred to as Programming Wizard). The Wizard has two options: Quick Setup - This method allows you to manually configure the basic setup for Screen, Input, Output and Wi-Fi. After the configuration setup, you are directed to the HOME screen of the device
Programming Wizard
The Programming Wizard is the initial Device Setup Wizard which appears automatically.
Wi-Fi Setup and Remote Access:
The Wi-Fi setup can be done during the Initial Setup Wizard, by importing the configuration from another device, or using the Quick Setup section. Note: The Admin password must be enabled for Wi-Fi setup to be accessed.
BUILDING THE METER
WIRING
PROGRAMMING
Press on the GEAR in the top right of the screen to see Login.
Enter Admin password and click on Login.
At the SYSTEM Icon , click on the DEVICE Icon
Click on Signal Input Configuration
Click on correct Input type. CURRENT the click right RED arrow.
Leave Input Sample Rate at default. Click the RED arrow.
Leave Display Update Rate at default. Click the RED arrow.
Enter the number of Decimals desired in the display. Click the RED arrow.
Leave ROUNDING at default. Click the RED arrow.
Leave OFFSET DISPLAY at 0.0. Click the RED arrow.
Leave Digital Filter at default. Click the RED arrow.
Leave Filter Band at default. Click the RED arrow.
Leave Scaling Points at 2. Click the RED arrow.
At Scaling Type, leave at Enter Values. Click the RED arrow.
At Scaling Point A1, change to 4.000. Click the RED arrow.
At Display Point A1, leave at 0.0. Click the RED arrow.
At Scaling Point A2, change to 20.000. Click the RED arrow.
At Display Point A2, change to what the MAX display should be. Click the RED arrow.
At Enable Scale List B, leave OFF. Click the RED arrow.
At show MIN/MAX Capture, leave OFF. Click the RED arrow.
Click on APPLY then click on the HOME Screen
This completes the programming of the Input.
Continue with the relay outputs if needed.