PLEASE NOTE:
When converting from the legacy CUB4CL unit to the current CUB5I there is an input signal range jumper under the rear cover that will need to be set for your application mA input level. Display scaling is also done via the front keypad not with scale potentiometers.
This article will discuss the conversion of a legacy CUB4CL unit to the current CUB5I model.
APPLICABLE PRODUCTS
CUB4CL20, CUB4CL40, CUB5IB00, CUB5IR00
PRE-REQUISITES
NONE
IN THIS ARTICLE
To complete the conversion of the legacy CUB4CL unit to current CUB5 units proceed as below.
- First if this application was using an input signal greater than 20 mA. Remove the rear cover of the CUB5I unit and set the input range jumper to the 200 mA position. See CUB5I product manual document for details.
- Connect the signal + wire to the input terminal of the CUB5I unit.
- Connect the signal – wire to the common terminal of the CUB5I unit.
- Connect the V+ wire to the +9-28 Vdc terminal of the new CUB5 unit.
- Please note There is no PROGRAM terminal on the current version of the CUB5 unit. That terminal when jumped to the common terminal allowed for program access. When removed, the unit is in Problem disable mode. That mode is also available in the new CUB5 unit and can be setup by programming USER IN as a PROLOC function. This is optional if a program disable feature is desired.
CUB4CLxx
CUB5Ixxx
ADDITIONAL INFO
CUB4CL manual cub4-lp-cl-product-manual.pdf
CUB5I manual cub5i-product-manual.pdf
Additional assistance needed? Contact us here.