Overview
This technical note explains how to configure a PM500A panel meter displaying a 4-20 mA pressure signal so that an operator can easily set the display to zero using an on-screen Function Key.
When configured correctly, pressing the TARE button will offset the current reading and display 0, allowing the operator to zero the displayed pressure without changing the input scaling.
Product
Application
A PM500A is being used to display pressure from a 4-20 mA transmitter. The user would like to create a Function Key that performs a Tare Display operation, allowing the displayed value to be reset to zero at any time.
Procedure
- Log in to the PM500A using the appropriate user credentials.
-
From the Home screen, navigate to:
System Display → Device Setup
-
Click the right arrow to access:
Function Configuration
- Select Function Configuration.
- Select Function Key Configuration.
- Set Enable Function Keys to ON.
- Click the right arrow and select F1.
- Click the right arrow again to access the key settings.
-
Rename the key to:
TARE
- Click the right arrow to access the function assignment.
-
Under Select Function, scroll down and choose:
Tare Display
- Click Apply to save the configuration.
- Return to the Home screen.
- Verify that the new TARE function button appears across the bottom of the display.
Verification
Press the TARE button on the Home screen.
Expected Result: The displayed pressure value is reset to 0, and subsequent readings are displayed relative to the tare point.
Notes
- The TARE function affects only the displayed value and does not alter the scaling configuration of the 4-20 mA input.
- If the TARE button does not appear on the Home screen, verify that Enable Function Keys is set to ON and that the configuration changes were successfully applied.
- Multiple function keys can be configured if additional operator functions are required.
HMS Support