Overview
This Tech Note explains how to configure a PM500A Panel Meter displaying pressure from a 4-20 mA transmitter so that a remotely mounted push button can perform a TARE (zero) operation. When the button is pressed, the displayed value is reset to zero, allowing the operator to establish a new reference point without accessing the meter setup menus.
Products
Application
- PM500A displaying pressure from a 4-20 mA input.
- Operator requires a remote push button to reset the display to zero (TARE).
- Useful for tank level, pressure, force, or process measurement applications where a temporary zero reference is needed.
Configuration Procedure
1. Navigate to User Input Configuration
- From the PM500A configuration software, select DEVICE.
- Click the Right Arrow to enter the device configuration.
- Select FUNCTION Config.
- Select USER INPUT Config.
- Click User Input.
- Select User Input 1 and click the Right Arrow.
2. Assign the TARE Function
- Locate the Function parameter.
- Scroll through the available functions.
- Select Tare Display.
- Click the Right Arrow to assign the function.
- Click Apply to save the configuration.
- Click the Home icon to return to the main screen.
Wiring the Remote TARE Push Button
Connect a momentary push button between the following PM500A terminals:
| Terminal | Connection |
|---|---|
| 11 | User Input |
| 13 | Common |
When the push button is pressed, the PM500A will execute the Tare Display function and reset the displayed value to 0.
Operation
After configuration and wiring are complete:
- Allow the pressure signal to stabilize.
- Press the remote TARE push button.
- The current displayed value becomes the new zero reference.
- Subsequent display values will be shown relative to this new zero point until another TARE operation is performed or the meter is reset.
Summary
By assigning User Input 1 to the Tare Display function and wiring a momentary push button between terminals 11 and 13, the PM500A can be remotely zeroed without entering the configuration menus. This provides a simple and convenient method for operators to establish a temporary zero reference directly from the machine or process location.