This article will discuss the required steps to scale the analog input of the IAMS series signal conditioners.
By default, the IAMS analog output follows the full-scale input. I.E. for 0-10V input, there is a 4-20ma output. This document describes how to scale the output over a different input range. The DSP LO and DSP HI will be based on the new limits; the analog output min and max limits will also follow the new display values.
NOTE: this is only applicable when a voltage or current input is used.
APPLICABLE PRODUCTS
- IAMS0001
- IAMS0011
- IAMS0002
- IAMS0022
PRE-REQUISITES
- One of the above IAMS models
- A PGMMOD05 programming module
IN THIS ARTICLE
Steps to rescale the analog output.
- Start by configuring the input signal and display values.
- Navigate to the ADV.SET section, select YES and press OK.
- Scroll to CAL SETUP press OK.
Configuring the Low Analog Value
* If not changing the low analog value, choose NO for CAL.LO and press OK, then skip to Configuring the High Analog Value section
- Select YES for CAL.LO and press OK.
- Apply the input signal that is associated with the low analog signal.
- Enter the display value associated with the current (low) input signal.
- Press OK.
Configuring the High Analog Value
* If not changing the high analog value, choose NO for CAL.HI and press OK, then skip to Selecting the Analog Output Scaling section
- Select YES for CAL.HI and press OK.
- Apply the input signal that is associated with the high analog signal.
- Enter the display value associated with the current (high) input signal.
- Press OK.
Selecting the Analog Output Scaling
- To use the new analog scaling: set USE.CAL to YES.
- To revert to the old settings: set USE.CAL to NO.
- Press OK.
Example
0-10 volt input, scaled 0-50.0, 4mA out at 2 volts, and 20mA out at 9 volts.
First, scale the input to read 0-50.0 for a 0-10V input, then proceed to the advanced section and perform the following:
ADV.SET YES
OK
CAL / SETUP
OK
CAL.LO YES
OK
Apply 2 volts
Enter 0
OK
CAL.HI YES
Apply 9 volts
Enter 50.0
OK
USE.CAL YES
OK
The unit is now setup for the example range and ready for use.