This article will discuss the two options for activating program lockout on the PXU control. You can program one of the units rear USR inputs as PLOC ( program lockout) in menu 1-IN. and activate the lock by placing a jumper on the USR and common terminals.
The other method is using a three-digit CODED or PIN.
APPLICABLE PRODUCTS
- PXU series process controllers
PRE-REQUISITES
- Any PXU series control
IN THIS ARTICLE
Discussion on the two methods available to enable program lockout on the PXU process control.
Method 1
Enter the Program follow the instructions to gain access:
-
Press the P button until CODE is displayed. If you do not have a jumper on one of the units rear USR inputs and do not know the current PIN number. 111 is the master unlock PIN.
-
When CODE is displayed, enter 111 by holding down the UP arrow button. Then press the P button.
-
You should know have program menu access. There is a total of nine program menus. For functions see the PXU manual which is linked below.
- You can set the PIN CODE of your choice in menu 1-IN under the CODE parameter. A range from -125 to 125 can be programmed.
Method 2
USER Inputs settings:
-
If a USER input is programmed for PLOC in menu 1-IN. You must remove one end of the jumper that is installed.
- The terminals will change in relation to the DIN size of the Controller. Below is the USR input terminals used on the PXU Controllers:
1/ 16 Din = Terminals #13 & #14 = USR 1 or Terminals #15 & #16 USR 2
1/8 or 1/4 Din = Terminals #20 * #21 USR 1 or Terminals #18 & #19 = USR 2
ADDITIONAL INFO
PXU manual pxu-manual.pdf