E3 I/O Module Spare Parts
E3 Replacement Terminal Blocks
| # of Pins | PT # | Description |
| 4 | KPTV0041 | RS485 terminal |
| 6 | KPTV0061 | Power Input Terminal |
| 17 | KPTV0171 | I/O Terminal for E3-MIX24880, E3-MIX24882, E3-32DI24, E3-32DO24, E3-32AI20M, E3-32AI10V, E3-16DI24, E3-16DIAC, E3-16DO24, E3-8AO20M, E3-16AI20M, E3-16AI8AO, E3-16ISOTC, 16ISO20M, E3-10RTD |
| 18 | KPTV0181 | E3-MIX20884 |
E3 Replacement Feet
See page 2-21 of E3 hardware user manual.
| QTY per E3 | PT # | Description |
| 2 | KHM04404 | Phillips screw for Din-rail\panel mount feet |
| 2 | KME3FT01 | Din-rail\panel mount feet |
E3 Replacement Din-rail clip
| QTY per E3 | PT # | Description |
| 1 | KME3CLP1 | Din-rail clip |
| 1 | KHXSPRG1 | Din-rail clip spring. |
-
Slide a Din rail clip (KME3CLP1) into the base as shown. You should be able to see the spring retention clip.
-
Place one end of the spring (KHXSPRG1) over the retention pin and compress the other end under the clip with a small flat head screw driver
-
The din rail clip should extend and retract when pushed downward
SixTRAK Spare Parts
Products:
ST-IPm-8460/ST-IPm-x350/VT-IPm-x410/ST-GT-1210/ET-GT-ST-3
| Replacement Part Number | Description |
| KHXSTIOS | Din Clip Spring |
| KMSIX000 | Plastic Din Clip |
| KDIPMST8 | Main decal on front of ST-IPm-8460 |
| KPTV0173 | Vertical screw terminal with 17 positions and locking screws for ST-IPm-8460. |
| KHX425PH | Case screw with lock washer for ST-IPm-8460, ST-IPm-6350, ST-IPm-x350, VT-IPm-x410, ST-GT-1210, ET-GT-ST-3 |
| D-IPM-ST-1 | Main Decal for the ST-IPm-6350 |
| KPTC0170 | Vertical Screw Terminal with 17 positions and no locking screws for ST-IPm-x350 and VT-IPm-x410 |
- Enter spring into Din Clip
- Slide clip into plastic.
VersaTRAK Spare Parts
Products:
VT-mIPm-138-D/VT-mIPm-248-D/VT-mIPm-245-D/VT-mIPm-135-D/VT-IPm2m-213-D/VT-IPm2m-113-D/VT-uIPm-431-H
| Replacement Part Number | Description |
| VT-IPM2M-113-DB | Replacement BASE for VT-IPM2M-113 |
| VT-IPM2M-113-M | Module ONLY VT-IPM2M-113 |
| VT-IPM2M-213-DB | Replacement BASE for VT-IPM2M-213 |
| VT-IPM2M-213-M | Module ONLY VT-IPm2m-213 |
| VT-MIPM-135-DB | Replacement BASE for VT-MIPM-131 |
| VT-MIPM-135-M | Module ONLY VT-MIPM-131 with IPM-CPU-5 |
| VT-MIPM-245-DB | Replacement BASE for VT-mIPm-245-D |
| VT-MIPM-245-M | Module ONLY VT-MIPM-245 with IPM-CPU-5 |
| VT-UIPM-431-HB | Replacement BASE for VT-UIPM-431 |
| VT-UIPM-431-M | Module ONLY VT-UIPM-431 with IPM-CPU-1 |
| KHXSTIOS | Din Clip spring |
| KMSTCLP2 | Din rail plastic clip |
| KDMPM241 | VT-mIPm-245-D front label |
| KDMPM248 | VT-mIPm-248-D front label |
| KDMPM138 | VT-mIPm-138-D front label |
How to change the front label
- Remove the VT RTU module from the base by pressing in on both sides.
- Slide a small flathead screw driver on one side of the module to release the plastic latches.
- While holding the side open. Slide a small flathead screw driver in the side slot on the other side. Remove the top half of the module.
- Slide out the existing label and slide in the new label.
- Replace the top half and press down until it snaps into the please.
How to replace a VersaTRAK IPm Module or Base
Replacement Module
- VersaTRAK IPm bases contain the IP address and serial number configuration but not the program, I/O Transfers, etc.
- Replace the module by removing power. Then remove the module from the base. Plug in the replacement module.
- Load the configuration and program from the Sixnet I/O Tool Kit configuration software via Ethernet or serial.
Replacement Base
- The base component holds the communication serial number and communication parameters. When replacing the base update the Sixnet I/O Tool Kit configuration with the new serial number and reload via serial.
- Remove power. Unwire the old base and re-wire the replacement base.
- Load basic configuration via Port B using the included RJ45-DB9F-IPm and a straight-thru Ethernet cable.
EtherTRAK-2 Spare Parts
Products
E2-MIX24880-D/E2-MIX24882-D/E2-MIX20884-D/E2-8AO20M-D/E2-32AI20M-D/E2-32AI10V-D/E2-32DI24-D/E2-32DO24-D/E2-16AI20M-D/E2-16AI-8AO-D/E2-16DI24-D/E2-16DIAC-D/E2-16DO24-D/E2-16DORLY-D/E2-16ISO20M-D/E2-16ISOTC-D/E2-10RTD-D
| Replacement Part Number | Description |
| E2-10RTD-M | Module only |
| E2-16DORLY-M | Module only |
| E2-16ISO20M-M | Module only |
| E2-16ISOTC-M | Module only |
| E2-8AO20M-M | Module only |
| E2-32DI24-M | Module only |
| E2-BASE-1 | Replacement base for all E2 module except E2-MIX20884-D/E2-16ISO20M-D/E2-16ISOTC-D. |
| E2-BASE-TC-1 | Replacement base for E2-16ISOTC-D |
| E2-BASE-20M-1 | Replacement base for E2-16ISO20M-D |
| E2-HLDDN-2 | Set of clips (2 per module) help keep the module steady in high vibration environments. Not required for high vibration environments. |
| RJ45-DB9F-CBL | One pre-wired RJ45-DB9F-IPm and two (one male one female DB9) unwired for user-configured pin-out. |
| KME2CLP1 | Red, short base clip. To secure the base to the din-rail when the I/O Module is mounted parallel to the din-rail. |
| KME2CLP2 | Red, long base clip. To secure base to the din-rail when the I/O Module is mounted perpendicular to the din-rail. |
| KME2CLP0 | Red Module clip to secure module to base. Two per module. |
| KME2KEY0 | Module key; two per module. |
| KME2KEY1 | Base key; two per base. |
How to replace a EtherTRAK-2 Module or Base
Replacement Module
- The EtherTRAK-2 base stores all the configuration parameters. To replace a module power down the unit, unplug existing module and plug-in new module.
- Once powered up the module will be operational again.
Replacement Base
- Power down the I/O Module and base. Unwire the base and rewire the new one.
- Plug the old module into the replacement base. Load the configuration from the Sixnet I/O Tool Kit via Ethernet.
Need Further assistance? Submit a support ticket here.